Installation Instructions

14
Connection, safety valve and condensate drain
The condensate pipe is connected to
the discharge pipe of the safety valve.
The condensate hose supplied meets
the temperature requirements that are
part of the CE certification.
Connecting the condensate pipe inter-
nally to the domestic waste water sys-
tem, either directly or via a tundish or
washing machine trap, is recommen-
ded.
If the condensate pipe is routed out-
side the building, use a pipe of at least
7
30 mm and insulate it against frost.
Avoid long outdoor pipework.
!
Please note
Frozen condensate pipes can
result in faults and damage to
the boiler.
Always insulate condensate
pipes against frost.
Observe local building regulations.
Connect the condensate pipe
A
with a
constant fall and a pipe vent to the public
sewage system.
Observe the local waste water regula-
tions.
Note
Fill the siphon with water before com-
missioning.
Installation sequence
Fitting the boiler and making connections
(cont.)
5609 059 GB