Technical data
7
5608 490 v1.2
Vitocell 300-V Installation Instructions
- For narrow passageways, remove upper and lower
portion of crating and carry DHW tank to its installation
location by means of crating boards mounted on the tank.
- Position tank carefully and remove wood crating.
- Leave adequate clearance to the wall or other objects
enabling easy access to the aquastat (where applicable).
- Install tank(s) on flooring or foundation capable of
supporting the weight of the tank(s) filled with water.
- The tank does not require a special foundation and can
be placed directly on the floor. If, for cleanliness
purposes, the tank is to be kept off the floor, a
foundation can be used for each tank or group of tanks.
Recommended service clearances
Rear in. (mm) 18 (460)
Sides May be reduced if rear pipe connections can
be reached with less clearance
in. (mm) 12 (300)
Top in. (mm) 12 (300)
Front in. (mm) 24 (600)
Minimum clearances to combustibles
All sides in. (mm) 0 (0)
Floor combustible
IMPORTANT
Provide sufficient clearances towards the wall to allow
the aquastat to be operated (if installed).
CAUTION
Install the DHW tank in a frost-protected and draft-free
room. Otherwise it must be drained when not in use, in
order to reduce the risk of damages caused by freezing.
Tank Set-up
Set-up and Connections
1. Apply Loctite 55 as per supplied instructions to each
tank nipple. Use Loctite 55 provided in the installation
fittings package.
2. Connect female ends of brass adaptors to the tank
nipples.