Technical Data Manual Model Nos. and pricing : See Price List VITOCELL 100-VH/-BH r Product may not be exactly as shown NCVA and NCVB Series Indirect-fired domestic hot water storage tank with one or two heat exchanger coils. With or without an optional electric heating element. Storage capacity: 79 USG (300 L) 119 USG (450 L) 5470 954 v1.
Product Information Vitocell 100-VH/-BH Technical Data Vitocell 100 Benefits at a glance: Upright storage tank made of steel S235JR with one or two large surface bare-tube heat exchangers. Glass-lined (enameled) tank in accordance with DIN 4753 part 3 on the inside, primer coated on the outside. Vitocell 100, NCVB-BH series for a dual-mode DHW heating with solar panels in conjunction with a boiler. Magnesium protection anode of 1a in.
Product Information Vitocell 100-VH/-BH Technical Data Connections Legend A DCW connection B Solar - Return (lower coil) C Sensor sleeve D Solar - Supply (lower coil) E Heating - Return (upper coil) F Recirculation G Heating - Supply (upper coil) 5470 954 v1.1 Connections H I J K L M N c in.
Specifications Vitocell 100-VH/-BH Technical Data Technical Data Model # Coil(s) Vitocell 100-VH NCVA Vitocell 100-VH NCVA Vitocell 100-BH NCVB Vitocell 100-BH NCVB Upper/Lower Upper/Lower Lower Lower Storage Capacity USG L 79.2 300 119 450 79.2 300 119 450 Water Content Heating Circuit USG L -- -- 1.3 5.6 2.5 9.4 Water/Glycol content Solar Circuit USG L 2.5 9.4 3.1 11.9 2.5 9.4 3.1 11.9 Tube Length (top) ft. m -- -- 24.9 7.6 37.1 11.3 Tube Length (bottom) ft. m 37.1 11.
Specifications Vitocell 100-VH/-BH Technical Data Technical Data (continued) For DHW production in conjunction with solar systems and heating boilers, and heating systems without low limit for dual coil operation. Suitable for heating systems with: max. working pressure on heat exchanger side up to 230 psig at 230° F (110° C) max. working pressure on DHW water side of up to 150 psig at 210° F (99° C) max. testing pressure on DHW side of 300 psig Vitocell 100-VH NCVA Vitocell 100-VH NCVA 79.
Specifications Technical Data Vitocell 100-VH/-BH Technical Data (continued) For DHW production in conjunction with solar systems and heating boilers, and heating systems without low limit for dual coil operation. Suitable for heating systems with: max. working pressure on heat exchanger side up to 230 psig at 230° F (110° C) max. working pressure on DHW water side of up to 150 psig at 210° F (99° C) max.
Specifications Vitocell 100-VH/-BH Technical Data Flow Rate A Lower coil, 119 USG (450 L) capacity A 79 USG (300 L) B 79 USG (300 L) Lower coil and 119 USG (450 L) Upper coil B 119 USG (450 L) 5470 954 v1.
Specifications Vitocell 100-VH/-BH Technical Data Dimensions Vitocell 100-VH, NCVA 8 Vitocell 100-BH, NCVB Vitocell 100-BH, NCVB 5470 954 v1.
Vitocell 100-VH/-BH Technical Data System Design Installation Example Heating system connection 5470 954 v1.
System Design Installation Example Vitocell 100-VH/-BH Technical Data (continued) Solar connection Legend 10 Solar collector Vitocell 100 Filling valve Solar-Divicon (pumping station) Recirculating pump Anti-scald tempering valve Heating circuit Oil/Gas-fired boiler Domestic cold water Domestic hot water Temperature and pressure relief valve 5470 954 v1.
System Design Vitocell 100-VH/-BH Technical Data System Design Sensor well Electric heating element 4.5 kW The stainless steel sensor wells are to be used for control sensors to ensure maximum operational safety. The top sensor well is used for the DHW sensor connected to the boiler control. The optional screw-in electric heating element is used in enameled solar and domestic water storage tanks as auxiliary or emergency heating. It should be mounted in a horizontal position by heating contractor.
Vitocell 100-VH/-BH Technical Data 5470 954 v1.1 Technical information subject to change without notice. Printed on environmentally friendly (recycled and recyclable) paper.