Technical data

98
Initial start-up
Further step-by-step instructions
(continued)
Checking outputs (actuators) and sensors
Vitotronic 100
Relay test
1. Press 9 and simultaneously for
approx. two seconds.
2. Select the relay outputs
with or .
3. Press .
The following relay outputs may be selected:
Display
indication
Relay function
11
Burner or stage 1 ON
12
Burner stage 1 and 2 ON or modulation up
13
Burner modulation neutral
14
Burner stage 1 ON (modulation down)
15
Output 20 ON
16
Output 29 ON
17
Output 52 open
18
Output 52 neutral
19
Output 52 close
11
Central fault message ON
Check sensors
1. Press .
Scanning operating conditions is
active, see page 106.
2. Scan the actual temperature with
or .
3. Press .
Scanning is completed.
5351 340 v1.4