Technical data

96
Initial start-up
Further step-by-step instructions
(continued)
Matching the control unit to a two stage burner (Vitotronic 100, GC1)
1. Start up the burner.
2. Set the override switch to .
3. Determine the maximum burner
output through the fuel
consumption.
Record the relevant value.
4. Set the override switch
to a.
5. Press 9 and simultaneously for
approx. two seconds.
Relay test is activated.
6. Activate the burner stage 1 ON
function with (display shows: 4).
7. Determine the minimum burner
output (basic load) through the fuel
consumption.
Record the relevant value.
8. Press .
Relay test is completed.
9. Set the determined values in
coding 1, see the table below and
page 154.
Address Setting the:
08 Units and tens of the determined maximum output;
e.g. max. output: 225 kW set here: 25
values including 199 kW can be entered directly
09 Hundreds of the determined maximum output;
e.g. max. output: 225 kW set here: 2
0A Relationship between basic output and max. output in percent; e.g.
basic output: 135 kW
max. output: 225 kW
135 kW
225 kW
x100 % = 60 %
5351 340 v1.4