Technical data

95
Initial start-up
Further step-by-step instructions
(continued)
Matching coding addresses to respective system version
Vitotronic 100
In coding 1, set the following coding
addresses:
01 Multi-boiler system
02 Burner type
03 Oil or gas operation
07 Boiler number
In coding 2, set the following coding
addresses:
0C Return temperature control
0d Therm-Control
4C Function plug
4d Function plug sL
4E Function plug gS
77 LON participant number
98 Viessmann system number
9C LON participant monitoring
Vitocontrol-S, VD2/CT3/CM2
In coding 1, set the following coding
addresses:
00 System design
35 Number of boilers in the cascade
36 Minimum supply temperature limit
of the cascade
37 Maximum limit of the cascade
supply temperature
3b Control type
3C Control strategy
40 Actuator run time
A2 DHW priority
A5 Heating circuit pump logic
function (economy circuit)
C5 Minimum limit of the heating
circuit supply temperature
C6 Maximum limit of the heating
circuit supply temperature
In coding 2, set the following coding
addresses:
39 Permanent lead boiler
3A Permanent last boiler
4C Function plug
4d Function plug sL
4E Function plug gS
55 Function DHW temperature
control
77 LON participant number
7A Central control
7E Flue gas cascade
7F Detached house or apartment
building
98 Viessmann system number
9C LON participant monitoring
5351 340 v1.4