Technical data

91
Initial start-up
Further step-by-step instructions
Checking the heating circuit allocation (Vitocontrol-S, VD2/CT3/CM2
)
Check whether the label for heating
circuit allocation has been affixed to
the corresponding field of the
programming unit.
Press the corresponding button
before commencing any adjustments.
Changing the display language selection (Vitocontrol-S, VD2/CT3/CM2)
1. Press .
2. Select the required language
with .
3. Confirm with .
Checking the fixed high limit (Vitotronic 100)
Hold down the test button (TÜV)
during this test (in the h position); a
minimum supply rate must be present.
The minimum boiler flow rate should be
10% of the boiler flow rate at rated
output.
Reduce the heat consumption as far as
possible. The adjustable high limit R is
now bypassed.
The burner remains switched ON until
the boiler water temperature has
reached the safety temperature and the
fixed high limit (FHL) has switched
OFF.
After the burner has been shut down
by the fixed high limit,
Release TÜV button , the display will
show fault D4.
Wait until the boiler water
temperature has fallen 15 to 20˚C /
25 to 35˚F below the set safety
temperature, then reset the fixed high
limit by pressing button E; fault D4
will clear from the display.