Technical data

43
Installation – Vitotronic 100, GC1
Connection of the return temperature sensor
Strap-on temperature sensor and immersion temperature sensor
For measuring the supply and return
temperature.
Electrical connection
The sensor is inserted in socket ”17A”
or ”17B” on the control unit.
Check the sensor
1. Disconnect plug aJA or aJB in
the terminal compartment.
2. Measure resistance of sensor at
terminals ”1” and ”2” of the plug.
Flow/return
temperature
in °C / °F
Resistance
in
30 / 86
40 / 104
60 / 140
569
592
643
3. Compare the value measured with
the current temperature. If the value
differs significantly, check
installation and, if necessary, replace
sensor.
Technical data
Degree of protection: IP 32
Ambient temperature
during operation:
0 to + 100°C
32 to + 212°F
during storage and transport:
–20 to + 170°C
- 4 to + 158°F
5351 340 v1.4
17A or 17B
17A or 17B
30 40 50 60 70 80 90
540
560
580
600
620
640
660
680
700
720
740
20 100
Resistance in
Supply temperature/return temperature in °C / °F
68 86 104 122 140 158 176 194 212