Technical data

42
Installation – Vitotronic 100, GC1
Connection of the boiler temperature sensor
The sensor measures the boiler water
temperature of the boiler.
The boiler temperature sensor is
installed at the same time as the boiler
insulation.
Check the sensor
1. Disconnect plug § in the terminal
compartment of the boiler control.
2. Measure resistance of sensor at
terminals ”1” and ”2” of the plug.
Boiler water
temperature
in °C / °F
Resistance
in
40 / 104
50 / 122
60 / 140
578
597
616
3. Compare the value measured with
the current temperature. If the value
differs significantly, check
installation and, if necessary, replace
sensor.
Technical data
Degree of protection: IP 32
Ambient temperature
during operation:
0 to + 130°C
32 to + 266°F
during storage and transport:
-20 to + 170°C
- 4 to + 158°F
Electrical connection
The sensors are ready to plug in. Insert
the boiler temperature sensor in socket
”3” of the boiler control.