Technical data

192
Appendix
Specification Vitotronic 100, GC1
Rated voltage: 120VAC
Rated frequency: 60 Hz
Rated current: 2 × 6 A~
Power
consumption: 5 W
Safety class: I
Protection: IP 20 D to
EN 60529, safeguard
through design and
installation
Function: Type 1B to
EN 60730-1
Permissible ambient temperature:
During operation:
0 to 40˚C.
32 to 104˚F.
Installation in living accommodation.
and boiler rooms (normal ambient. . .
conditions).
During storage and transport:
–20 to 65˚C
– 4 to 149˚F
Relay output rating at 120VAC for:
Switching
output : 2 FLA
*1
Shunt or boiler circuit
pump sL: 2 FLA
*1
Central fault
message : 2 FLA
*1
Isolation
valve gS: 1 FLA
*1
or constant return
temperature
control gS: 0.1 FLA
*1
Burner
Plug fA: 3 FLA
Plug
– two stage: 0.5 FLA
– modulating: 0.1 FLA
*1
Total max. 6A
~
.
Specification Vitocontrol-S, VD2/CT3/CM2
Rated voltage: 120VAC
Rated frequency: 60 Hz
Rated current: 6 A~
Power
consumption: 10 W
Safety class: I
Protection: IP 20 D to
EN 60529, safeguard
through design and
installation
Function: Type 1B to
EN 60730-1
Permissible ambient temperature:
During operation:
0 to 40˚C
32 to 104˚F
Installation in living
accommodation and
boiler rooms (normal
ambient conditions)
During storage and transport:
–20 to 65˚C
– 4 to 149˚F
Relay output rating at 230 V~ for:
Heating circuit pump
or.
primary pump.
DHW tank heating.
system :.
2 FLA
*1
.
DHW tank
heating.
pump sA: 2 FLA
*1
.
DHW
circulation
pump sK: 2 FLA
*1
Shunt or
distribution
pump sL: 2 FLA
*1
Central fault
message : 2 FLA
*1
Three-way return
valve or isolation valve
0.1 FLA
*1
*1
Total max. 6A
~
5351 340 v1.45351 340 v1.4