Technical data
163
Coding – Vitotronic 100
Burner switching differential
For adjustment, see coding 04 on page 156.
Switching differential 4˚C / 7˚F (coding 04: 0)
Heat demand-dependent switching differential
ERB50 function (coding 0 : 1)
Subject to heat demand, values between 6 and 12˚C / 11 and 22 °F result.
ERB80 function (coding 04: 2)
Subject to heat demand, values between 6 and 20˚C / 11 to 36°F result.
The heat demand-dependent switching differential takes the boiler load into account. The switching differential, i.e. the
burner operating time, changes based on current heat demand.
Resetting codings to the factory setting
1. Press w and rw simultaneously
for approx. two seconds.
2. Press D.
Confirm Base setting? “Yes” with
.
Select Base setting “Yes” or
Base setting “No” with or .
5351 340 v1.4
Burner
+2
ON
OFF
-2
Lower
heat demand
Average
heat demand
Higher
heat demand
Time
Set
Lower
heat demand
Average
heat demand
Higher
heat demand
Time
Burner
ON
OFF
+9
-3
Set
+3
Lower
heat demand
Average
heat demand
High
heat demand
Time
Burner
ON
OFF
+17
-3
Set
+3
Code 2
Cod. 2
1
2
3