Technical data
160
Coding – Vitotronic 100, GC1
Coding 2
(continued)
Coding in the factory setting Possible change
Boiler/burner
24: 0 No maintenance indication 24: 1 Maintenance indication in display (address is
automatically set and must be manually reset after
maintenance has been carried out)
Boiler/burner (two-stage)
26: 0
Burner fuel consumption (stage 1);
no count, if 26: 0 and 27: 0 have been programmed
26: 1
to
26: 99
Input of 0.1 to 9.9;
1 setting step
= 0.1 litre or
gallons/hour
*1
27: 0 27: 1
to
27:199
Input of 10 to 1990;
1 setting step
= 10 litres or
gallons/hour
*1
Boiler/burner
28: 0 No burner interval ignition 28: 1 The burner will be force-started for 30 seconds
after 5 hours
Boiler/burner (two-stage)
29: 0
Burner fuel consumption (stage 2);
no count, if 29: 0 and 2A: 0 have been programmed
29: 1
to
29: 99
Input of 0.1 to 9.9;
1 setting step
= 0.1 litre or
gallons/hour
*1
2A: 0 2A: 1
to
2A:199
Input of 10 to 1990;
1 setting step
= 10 litres or
gallons/hour
*1
General
2b: 5
Maximum pre-heating time of isolation valve:
5
m
i
n
u
t
e
s
2b: 0 No pre-heating time
M
a
x
i
m
u
m
p
r
e
-
h
e
a
t
i
n
g
t
i
m
e
o
f
i
s
o
l
a
t
i
o
n
v
a
l
v
e
:
5 minutes
2b: 1
to
2b: 60
Pre-heating time adjustable from 1 to 60 minutes
*1
The fuel consumption can only be scanned in conjunction with Vitosoft or Vitocom.
5351 340 v1.4