Technical data
157
Coding – Vitotronic 100, GC1
Coding 2
(continued)
Coding in the factory setting Possible change
Burner (mod.) (see page 97)
05: 70 Burner curve 05: 0 Linear burner curve
05: 1
to
05: 99
Non-linear burner curve
(see page 97):
P
T
in kW
P
max
in kW
= P
T
in %
P
T
Partial load at 1/3
of the burner
actuator operating
time
P
max
Maximum output
x 100
%
Boiler/burner
06: 87 Maximum boiler water temperature limit:
87˚C / 186˚F
06: 20
to
06:127
Maximum boiler water temperature limit
adjustable from 20 to 127˚C / 68 to 127˚F
Boiler
07: 1 Consecutive boiler number in multi-boiler systems
(in conjunction with coding address 01)
07: 2
to
07: 4
Consecutive boiler number in multi-boiler systems
(in conjunction with coding address 01)
Burner (two stage/mod.) (see page 96)
08:
*1
Maximum burner output
in kW
08: 0
to
08:199
Maximum output adjustable from 0 to 199 kW;
1 setting step = 1 kW
09:
*1
Maximum burner output
in kW
09: 0
to
09:199
Maximum output adjustable from 0 to 19
,,
900 kW;
1 setting step = 100 kW
0A:
*1
Burner base output
in percent
0A: 0
to
0A:100
P
G
in kW
P
max
in kW
= P
G
in %
P
G
Base output
P
max
Maximum output
x 100
%
*1
The factory setting is defaulted by the boiler coding card.