Technical data

155
Coding – Vitotronic 100, GC1
Coding 1
(continued)
Coding in the factory setting Possible change
Boiler/burner
06: 87 Maximum boiler water temperature limit:
87˚C / 189˚F
06: 20
to
06:127
Maximum boiler water temperature limit
adjustable from 20 to 127˚C / 68 to 261˚F
Boiler
07: 1 Consecutive boiler number in multi-boiler systems
(in conjunction with coding address 01)
07: 2
to
07: 4
Consecutive boiler number in multi-boiler systems
(in conjunction with coding address 01)
Burner (two stage/mod.) (see page 96)
08:
*1
Maximum burner output
in kW
08: 0
to
08:199
Maximum output adjustable from 0 to 199 kW;
1 setting step = 1 kW
09:
*1
Maximum burner output
in kW
09: 0
to
09:199
Maximum output adjustable from 0 to 19,900 kW;
1 setting step = 100 kW
0A:
*1
Burner base output
in percent
0A: 0
to
0A:100
P
G
in kW
P
max
in kW
= P
G
in %
P
G
Base output
P
max
Maximum output
x 100
%
Burner (mod.) (see page 97)
15: 10 Burner actuator run time:
10 seconds
15: 5
to
15:199
Operating time adjustable from 5 to 199 seconds
for Vitocrossal 300 with MatriX burner
Set
Type CM3 and CU3: 15: 64
Type CV3: 15: 19
General
40:125 Actuator operating time for isolation valve,
three-way mixing valve or mixing valve motor in
conjunction with return temperature control
125 seconds
40: 5
to
40:199
Operating time adjustable from 5 to 199 seconds
77: 1 LON participant number 77: 2
to
77: 99
LON participant number, adjustable from 1 to 99
Please note:
Allocate each number only once.
*1
The factory setting is defaulted by the boiler coding card.