Technical data
117
Troubleshooting – Vitocontrol-S, VD2/CT3/CM2
Faults displayed at the programming unit
(continued)
Fault display in plain text
Ext. fault
Outdoor temperature sensor
Supply sensor
Boiler 1 to 4
DHW tank sensor (1 or 2; display
only, if a second DHW tank
temperature sensor is connected)
Return sensor
Sensor 17A
Sensor 17B
Room temperature sensor
Flue gas sensor
Collector sensor
Solar DHW sensor
Participant No.
Participant fault (display only if
control unit is programmed as fault
manager)
Calling up acknowledged fault
messages
Press for approx. 3 seconds. The
fault will then be displayed.
Select the acknowledged fault
with or .
Fault
code
System characteristics
Cause Remedy
0
00
0f
ff
f
Control mode Maintenance
“0F” is only displayed in error
history
Carry out maintenance
Please note:
After maintenance, set coding 24: 0
1
11
10
00
0
Activates after 0˚C / 32˚F outdoor
temperature
Short circuit
Outdoor temperature sensor
Check outdoor temperature sensor
(see page 143)
1
11
18
88
8
t
e
m
p
e
r
a
t
u
r
e
Open circuit
Outdoor temperature sensor
2
22
20
00
0
Vitocontrol-S, VD2/CT3/CM2
controls in a stand-alone manner
w
/
o
s
u
p
p
l
y
t
e
m
p
e
r
a
t
u
r
e
s
e
n
s
o
r
Short circuit
Common supply temperature sensor
Check common supply temperature
sensor (see page 142)
2
22
28
88
8
w
/
o
s
u
p
p
l
y
t
e
m
p
e
r
a
t
u
r
e
s
e
n
s
o
r
(supply temperature may not be high
enough)
Open circuit
Common supply temperature sensor
4
44
40
00
0
Mixing valve closes Short circuit
Supply temperature sensor of
mixing valve circuit M2
Check supply temperature sensor
(see page 142)
4
44
44
44
4
Short circuit
Supply temperature sensor of
mixing valve circuit M3
4
44
48
88
8
Open circuit
Supply temperature sensor of
mixing valve circuit M2
5351 340 v1.4