Operating instructions
Filling the burner trough
When the system has been switched off properly, there is 
no more fuel in the burner trough or in the underfeed auger.
With the fire block cooled down (combustion chamber 
temperature below 482° F (250° C), touching soft touch 
key 1 “Boiler ON” will automatically fill the burner trough 
with fuel. 
Heating up
Light a fire with paper and kindling wood in the 
combustion chamber. After this, use a shovel to push 
the fire back to the filled burner trough. Then press Soft 
touch key 1 “Boiler ON” again (Soft touch key 1 “Boiler 
ON” is then dark green). Operating mode “HEAT UP” 
shows in the upper left of 
the display.
Fuel >W 40
-  With fuel that has water content greater than W40, 
  preheat the boiler with a chopped wood fire. To do 
  so, manually light chopped wood in the combustion 
  chamber and use a shovel to push it into the burner 
  trough. If necessary, add more chopped wood. Heat 
  up the fireclay brick lining like this for approx. one 
 hour.
-  Starting up the facility: Soft touch key 1 “Boiler ON”
  The soft touch key “Underfeed ON” is for manually 
  activating the underfeed auger in automatic operation 
  (= manual prompt for material). As long as this soft 
  touch key is touched, the underfeed auger conveys 
  fuel into the burner trough. With the underfeed auger 
  stopped (soft touch key “Stop underfeed” light-grey), 
  the manual prompt for material cannot be activated.
5603 882 - 01
Check heat up successful
The combustion chamber temperature should be over 356° 
F (180° C) in 30 minutes (adjustable value). Otherwise 
the system will automatically shut down. In such case 
press Soft touch key 1 “Boiler ON”.
Heating up with automatic ignition
The boiler is simple to switch on:
-  Press Soft touch key 1 “Boiler ON”. The loader
  modules will be switched on in the appropriate order. 
  When the auger filling time or combustion chamber 
  filling time has lapsed and there is enough fuel in the 
  combustion chamber, the loader system switches off.
-  The automatic ignition then takes place. The ignition 
  process stops as soon as the fire is started.
  The boiler then automatically switches to full load 
  operation. (If the material should be too moist, it
  might be necessary to proceed following section 
  “Heating Up” above.)
 Heating Up Manually
 Technical information subject to change without notice. Printed on environmentally friendly 
(recycled and recyclable) paper.
Pyrotec Installation & Operating