Operating instructions
46
5603 882 - 01
Pyrotec Installation & Operating
 Boiler Wiring
CAUTION
The information about wire type, wire number and wire 
gauge made in the wiring diagrams is not obligatory. The 
final decision of these settings has to be made by the 
executing installation company taking into consideration 
the local codes and regulations.
CAUTION
Any alteration of the control cabinet will void the warranty.
-  Lines arranged in metal pipe with minimum distance 
  of 6 in. (150 mm) to the base. Use support with cable 
  routing for light barrier. No support on base.
-  Screw cable channel (metal design) onto the foot plate
  on top of the boiler with minimum distance of b in. 
 (10 mm).
-  Fasten cable channel (metal design) on casing with 
  minimum distance of c in. (20 mm).
-  Cable channel (metal design) over entire width of boiler: 
  fastening on the bottom of the boiler jacket (it is not 
 water-bearing).  
-  Mount cable channel (metal design) with minimum 
  distance of 7c in. (200 mm) to the feed auger: 
  no support on the feed auger.
-  Arrange lines in protective cable hose with sufficient 
  leeway to open and close the door (mind the door stop).
Electrical
CAUTION
The Viessmann supplied field wiring diagram is not a 
complete system drawing. It is the installer’s responsibility 
to assure that the control is suitable for the respective 
installation, and all necessary safety equipment is installed.