Technical data

Malfunction report / malfunction remedy
Pyrot ECO 2005-05-01_E Page 2 of 2
Loader System
No.
Text displayed for malfunc-
tion
Malfunction alarm Possible cause Check / Remedy
01
Material shortage
(F4 lights up red)
- Light barrier in the metering container
- Light barriers for the ember monitoring sys-
tem
- Silo is empty
- Material clogged
- Fill silo
- Switch off master switch and undo material clogging
- Acknowledge with OK
11-24
Starttec …
(F4 lights up red)
- Starttec (motor starter mounted on clipboard
for the motor)
- Red lamp on the Starttec lights up
- Phase sequence mixed up
- Motor overloaded
- Other causes, depending on the malfunction dis-
played.
- Correct the phase sequence (clockwise rotating magnetic field)
- Undo clogging; make motor smooth-running
- Refer to documentation for Starttec
- Acknowledge with OK
30
Feed auger
(F4 lights up red)
- Reversed control of feed auger - Material clogging in the feed auger - Undo material clogging
31-45
Conveyor device …
(F4 lights up red)
- Maintenance cover limit switch
- One of the maintenance covers is open or not closed
properly.
- Check and close all the maintenance covers.
- Acknowledge with OK
51-52
Extraction system …
(F4 lights up red)
- Maintenance cover limit switch
- One of the maintenance covers is open or not closed
properly.
- Check and close all the maintenance covers.
- Acknowledge with OK
53-54
Extraction system … Hydraulic
drive, temperature/level
(F4 lights up red)
- Level float switch in the oil container for the
sliding bar extraction system
- Thermostat in the oil container
- Oil level too low, (possible loss of oil)
- Oil has been overheated by too high a pressure.
- Refill oil. Check oil line for leakage
- Check and adjust operating pressure (by KÖB)
- Acknowledge with OK.
53-54
Extraction system … silo door
open
(F4 lights up red)
- Limit switch for silo door - Silo door open
- Check and close silo door.
- Acknowledge with OK.
Heat Distribution
No.
Text displayed for malfunc-
tion
Malfunction alarm Possible cause Check / Remedy
01-27
Interruption or short-circuit,
sensor . . .
(F… lights up red)
- Sensor . . .
- Damage to the sensor connecting line
- Malfunction alarm defective
- Call in electrician