Technical data
22
Exhaust gas deduster, detached (optional)
IMPORTANT: Never operate the boiler without
ash container!
Pneumatic tube-cleaning system (optional)
- Operation and maintenance of the compressor
(optional) according to the manual that comes
with the facility.
- The timer that comes with the compressor is for
limiting the running time and should be
mounted between the compressor and the
power supply.
- When the compressed air system is provided
by the customer, the compressor has to be
suited for continuous operation or be secured
against continuous operation (e.g. timer for lim-
iting running time).
- Continuous operation of the compressor indi-
cates leakage in the air system. Check air sup-
ply line and valves for leakage.
After approx. 1000 operating hours:
Unplug the plug, unscrew butterfly nuts, pull
out motor with impeller and clean with broom
or wire brush.
CAUTION: DANGER OF INJURY – be abso-
lutely sure to switch off master switch.
After each cleaning of the set of tub-
ing
Open lid and clean the guide blades of
the de-duster with hand-brush.
After approx. 300 operating hours (90-
litre ash bin):
Empty ash bin beneath the de-duster.
Regularly drain condensation water in the
compressed air distribution bar.