5.4.4 Additional heat generator
Function (ECO-KP1):
The additional heat generator is automatically connected
when required. This takes place after the system tempera-
ture is fallen short of that is set for covering the entire
heat requirement or a peak in heat requirement. A boiler
plant group is required to carry off heat for the additional
boiler that will simultaneously provide for maintaining the
return flow.
Operating modes:
- Off:
The additional heat generator is switched off.
- Automatic:
Automatic clearance of the additional heat generator
when either an adjustable connecting temperature for
the accumulator is fallen short of or a sensor for the
forward flow bar.
- On:
Additional heat generator cleared.
- Manual:
Additional heat generator cleared and pump on; the
valve is not controlled (emergency operation).
(screen number) parameter (factory setting)
(01) Operating mode (automatic)
Select operating mode
(02) Delay before connecting (15 min)
Clearance is given when the time set is up.
(03) Connecting temperature, system set-point tempera-
ture (-15°C)
If the system temperature falls by this amount below the
system set-point temperature, the delay before connecting
(screen 2) begins to lapse.
(04) Switch-off temperature for system set-point tempera-
ture (-5°C)
Switch-off difference in parallel operation
(07) Set-point temperature of return flow (50°C)
Desired temperature of return flow
(09) Load storage unit to (storage unit at top):
To which heat storage sensor should the storage unit be
loaded?
(Indication only with accumulator option)
(10) Load storage unit to (70°C):
To what temperature on the accumulator sensor selected
should the additional heat generator heat up the accumula-
tor?
(Indication only with accumulator option)
(12) Service function of additional heat generator
A maintenance function for the specialist
(13) Operating hours counter