Technical data

Note: The control system components below are reserved for the PYROT Single-unit System.
With the PYROT Double-unit System, these functions are included in the Mastercontrol.
Accumulator Management System 3 Sensors [Item No: ECO-KSF3]
Function:
With a heat exchanger used, the modulating output operation by the PYROT Rotation Heating System is optimized. In
addition, short-term heat requirement peaks are covered. The heat accumulated in the accumulator is detected by a
temperature sensor. The heat input is adjusted to the degree to which the accumulator is charged.
Included in delivery:
- Two additional KTY sensors with dipping shell, 1/2 " x 280 mm (B28.2, B28.3, see Spec Sheet 6960-1)
Accumulator Management System, 5 Sensors (QM) [Item No: ECO-KSF5]
Function:
Using a heat accumulator improves the modulating output operation of the PYROT rotation heating system. In addition,
sudden heat requirement peaks are covered. The accumulator's load of heat is detected by the temperature sensors.
The instruction for the accumulator's degree of loading is carried out by the external sensor in weather-guided fashion.
The firing power is adapted to the accumulator's degree of loading.
Included in delivery:
- 4 additional KTY sensors with dipping shell, 1/2" x 280 mm (B28.2, B28.3; see Spec Sheet 6960-1)
Note: For Art. No ECO-KSF5, Article ECO-BM-00 or ECO-RM-00 is also necessary.
See Spec Sheets 4000 and 4020.
External Requirement ON/OFF [Item No: ECO-ANP]
Input for switching the system on and of automatically by an external floating make contact
Operational Message [Item No: ECO-KBM]
Function:
Output of the "Operating Load" operating condition, when the PYROT boiler is in operation to higher-level instrumentation
and control equipment for further processing
Included in delivery:
- Floating output (operational message)
Output signals 0 V - 10 V [Item No: ECO-KLS]
Function:
The system included in delivery output of the boiler output in the form of a voltage signal and preparation for connection
to receive a maximum limitation of the boiler output.
The following items come with the system:
- Output of the boiler output, 0 V - 10 V
- Reception and processing of an external output limitation
0 V - 0.5 V... OFF
0.6 V - 3 V... Standby
3.1 V - 10 V... 30% to 100% output operation
Note: Installation of "Output signals 0 V - 10 V" are possible according to "QM for Wood Heating Systems" irrespective of
any additional control system components to be used.
Spec Sheet
Pyrot Ecotronic Control System
Output Management System