Install Instructions
Table Of Contents
- ProPress stainless approved fluids
- ProPress stainless approved gases
- Dimensional data
- ½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- ¾" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1¼" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2½" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 3" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 4" Stainless Steel, ASTM A554 flow rate, velocity, loss
- Fitting friction loss equivalent length of tube (feet)
- MSS SP-58 or the maximum spacing and minimum rod sizes
- Minimum distance between press fittings
- ProPress standard jaws clearance requirements
- ProPress standard jaws clearance requirements between tube, wall, and floor
- ProPress compact jaws clearance requirements
- ProPress compact jaws clearance requirements between tube, wall, and floor
- ProPress rings dimensions
- ProPress rings with V1 actuator clearance requirements
- ProPress rings with V2 actuator clearance requirements
- ProPress rings with V1 actuator clearance requirements between tube, wall, and floor
- ProPress rings with V2 actuator clearance requirements between tube, wall, and floor
- ProPress rings with C1 actuator clearance requirements between tube, wall, and floor
- ProPress XL-C rings dimensions
- ProPress XL-C rings clearance requirements
- ProPress XL-C rings clearance requirements between tube, wall, and floor
- Minimum distance between existing soldered or brazed fitting and ProPress fitting
- Minimum distance between soldered fitting and ProPress fitting
- Minimum insertion depths for ProPress Stainless ½" to 2"
- Insertion depths for ProPress Stainless ½" to 2" no-stop couplings
- Minimum insertion depths ProPress Stainless 2½" to 4"
- Insertion depths for ProPress Stainless 2½" to 4" no-stop couplings
- About this Document
- Disclaimer
- Product Information
- Handling Instructions
- Installation Instructions
- Limited warranty
Installation Instructions
45 of 56
IM-PP 599834 0320 ProPress Stainless
Tube
Diameter
(inches)
Minimum In-
sertion Depth
(inches)
Minimum In-
sertion Depth
(mm)
Maximum In-
sertion Depth
(inches)
Maximum In-
sertion Depth
(mm)
½ ¾ 19 ⅞ 22
¾ ⅞ 23 1⅛ 28
1 ⅞ 23 1⅛ 28
1¼ 1 26 1
3
/
16
30
1½ 1
7
/
16
37 1
9
/
16
40
2 1
9
/
16
40 1¾ 44
Table 32: Insertion depths for ProPress Stainless ½" to 2" no-stop couplings
No-stop couplings and extended no-stop couplings are often used to
conduct repairs. Without a stop, these couplings can slide completely
onto a tube and allow a connection to be made in tighter spaces. Unlike
ttings with an integrated stop that have a minimum insertion depth, no-
stop couplings have minimum and maximum allowable insertion depths.
Both the minimum and the maximum insertion depths must be marked
and a line connecting the two marks.
▶ While turning slightly, slide press tting onto the tube to the marked
insertion depth.
Note: End of tube must contact stop.
▶ Pull retaining pin out of press tool.
▶ Insert appropriate jaw.
▶ Push in retaining pin until it locks the jaw in place.










