Install Instructions

Table Of Contents
Installation Instructions
42 of 56
IM-PP 599834 0320 ProPress Stainless
Tube
Diameter
(inches)
Soldering
minimum
distance (inches)
Soldering
Minimum
distance (mm)
Brazing minimum
distance (inches)
Brazing Minimum
distance (mm)
½ 38 114
¾ 57 172
1 3 76 9 229
95 11¼ 286
114 13½ 343
2 6 153 18 457
191 22½ 572
3 9 229 27 686
4 12 305 36 915
Table 30: Minimum distance between soldered 󶈵tting and ProPress 󶈵tting
The installer should take precautions to keep the Viega ProPress Stainless
connection cool:
Wrap the connection with a cold wet rag.
Protect the connection with a weld blanket.
Prefabricate solder connections/welded 󶈵ttings prior to installing the
press 󶈵tting. (Ensure tube has cooled before installing the 󶈵tting).
Apply heat sink gel or spray or spot freezing
4.5 Welding
To prevent damage to the sealing element, maintain proper welding
distances from the 󶈵tting. If welding adjacent to the connection, weld a
minimum of four inches away.
Installers should follow the precautions listed above to keep the Viega
ProPress Stainless connection cool.
4.5.1 Welding Adjacent to a Press Fitting