Install Instructions
Table Of Contents
- ProPress stainless approved fluids
- ProPress stainless approved gases
- Dimensional data
- ½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- ¾" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1¼" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2½" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 3" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 4" Stainless Steel, ASTM A554 flow rate, velocity, loss
- Fitting friction loss equivalent length of tube (feet)
- MSS SP-58 or the maximum spacing and minimum rod sizes
- Minimum distance between press fittings
- ProPress standard jaws clearance requirements
- ProPress standard jaws clearance requirements between tube, wall, and floor
- ProPress compact jaws clearance requirements
- ProPress compact jaws clearance requirements between tube, wall, and floor
- ProPress rings dimensions
- ProPress rings with V1 actuator clearance requirements
- ProPress rings with V2 actuator clearance requirements
- ProPress rings with V1 actuator clearance requirements between tube, wall, and floor
- ProPress rings with V2 actuator clearance requirements between tube, wall, and floor
- ProPress rings with C1 actuator clearance requirements between tube, wall, and floor
- ProPress XL-C rings dimensions
- ProPress XL-C rings clearance requirements
- ProPress XL-C rings clearance requirements between tube, wall, and floor
- Minimum distance between existing soldered or brazed fitting and ProPress fitting
- Minimum distance between soldered fitting and ProPress fitting
- Minimum insertion depths for ProPress Stainless ½" to 2"
- Insertion depths for ProPress Stainless ½" to 2" no-stop couplings
- Minimum insertion depths ProPress Stainless 2½" to 4"
- Insertion depths for ProPress Stainless 2½" to 4" no-stop couplings
- About this Document
- Disclaimer
- Product Information
- Handling Instructions
- Installation Instructions
- Limited warranty
Installation Instructions
50 of 56
IM-PP 599834 0320 ProPress Stainless
4.9 Pressure Testing
Viega Smart Connect technology provides a quick and easy way for
installers to identify connections that need to be pressed. Unpressed
connections are located by pressurizing the system with air or water.
Pressure test all installed tubing in accordance with local codes.
Smart Connect Testing
■ Testing for unpressed connections using Smart Connect
is not a replacement for pressure testing requirements
of local codes and standards.
■ If testing with compressed air, use an approved leak-
detect solution.
Water testing with Viega Smart Connect:
■ Use a range of 15 to 85 psi.
■ If an unpressed tting is found, make sure the tube is fully inserted
before completing the press.
■ If the initial test is successful, system may be pressure tested as
required up to 600 psi.
Testing with air can be dangerous at high pressures. When air testing with
Viega Smart Connect:
■ Use a range of ½ psi to 45 psi (static or dynamic).
■ If an unpressed tting is found, make sure the tube is fully inserted
before completing the press.
■ If the initial test is successful, system may be pressure tested as
required up to 200 psi (static).
4.10 Disposal
Separate the product and packaging materials (e.g. paper, metal, plastic,
non-ferrous metals) and dispose in accordance with all national, state,
and regional requirements.