Install Instructions
Table Of Contents
- ProPress stainless approved fluids
- ProPress stainless approved gases
- Dimensional data
- ½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- ¾" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1¼" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2½" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 3" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 4" Stainless Steel, ASTM A554 flow rate, velocity, loss
- Fitting friction loss equivalent length of tube (feet)
- MSS SP-58 or the maximum spacing and minimum rod sizes
- Minimum distance between press fittings
- ProPress standard jaws clearance requirements
- ProPress standard jaws clearance requirements between tube, wall, and floor
- ProPress compact jaws clearance requirements
- ProPress compact jaws clearance requirements between tube, wall, and floor
- ProPress rings dimensions
- ProPress rings with V1 actuator clearance requirements
- ProPress rings with V2 actuator clearance requirements
- ProPress rings with V1 actuator clearance requirements between tube, wall, and floor
- ProPress rings with V2 actuator clearance requirements between tube, wall, and floor
- ProPress rings with C1 actuator clearance requirements between tube, wall, and floor
- ProPress XL-C rings dimensions
- ProPress XL-C rings clearance requirements
- ProPress XL-C rings clearance requirements between tube, wall, and floor
- Minimum distance between existing soldered or brazed fitting and ProPress fitting
- Minimum distance between soldered fitting and ProPress fitting
- Minimum insertion depths for ProPress Stainless ½" to 2"
- Insertion depths for ProPress Stainless ½" to 2" no-stop couplings
- Minimum insertion depths ProPress Stainless 2½" to 4"
- Insertion depths for ProPress Stainless 2½" to 4" no-stop couplings
- About this Document
- Disclaimer
- Product Information
- Handling Instructions
- Installation Instructions
- Limited warranty
Installation Instructions
43 of 56
IM-PP 599834 0320 ProPress Stainless
Only cut stainless steel pipe with an approved stainless steel pipe cutter.
▶ Cut the tube square using a displacement-type cutter or ne toothed
saw.
Note: Cut tubing a minimum of four inches away from the contact area of
the vise to prevent possible damage to the tubing in the press area.
4.6 Cutting the Tube
Damaged tube and/or sealing element
Press ttings can form improper connections as the result
of damaged tube and/or sealing elements.
■ Do not use ame cutters when cutting the tube.
■ Do not use grease or oils when cutting the tube.
4.7 Deburring the Tube
Damage resulting from the wrong deburring tool
■ Connections may leak if they are damaged by improper
deburrer.
■ Failure to deburr the tube will reduce the service life of
the system and can cause premature leaks.
The tube ends must be thoroughly deburred after cutting. Damage to
or twisting of the sealing element during installation is prevented by
deburring.
▶ Deburr inside and outside of the tube to the proper insertion depths.
▶ Use a wire brush, Scotchbrite pad, sand cloth, or sandpaper to
remove loose dirt and rust particles from the pressing area.