Install Instructions
Table Of Contents
- ProPress stainless approved fluids
- ProPress stainless approved gases
- Dimensional data
- ½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- ¾" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1¼" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2½" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 3" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 4" Stainless Steel, ASTM A554 flow rate, velocity, loss
- Fitting friction loss equivalent length of tube (feet)
- MSS SP-58 or the maximum spacing and minimum rod sizes
- Minimum distance between press fittings
- ProPress standard jaws clearance requirements
- ProPress standard jaws clearance requirements between tube, wall, and floor
- ProPress compact jaws clearance requirements
- ProPress compact jaws clearance requirements between tube, wall, and floor
- ProPress rings dimensions
- ProPress rings with V1 actuator clearance requirements
- ProPress rings with V2 actuator clearance requirements
- ProPress rings with V1 actuator clearance requirements between tube, wall, and floor
- ProPress rings with V2 actuator clearance requirements between tube, wall, and floor
- ProPress rings with C1 actuator clearance requirements between tube, wall, and floor
- ProPress XL-C rings dimensions
- ProPress XL-C rings clearance requirements
- ProPress XL-C rings clearance requirements between tube, wall, and floor
- Minimum distance between existing soldered or brazed fitting and ProPress fitting
- Minimum distance between soldered fitting and ProPress fitting
- Minimum insertion depths for ProPress Stainless ½" to 2"
- Insertion depths for ProPress Stainless ½" to 2" no-stop couplings
- Minimum insertion depths ProPress Stainless 2½" to 4"
- Insertion depths for ProPress Stainless 2½" to 4" no-stop couplings
- About this Document
- Disclaimer
- Product Information
- Handling Instructions
- Installation Instructions
- Limited warranty
Installation Instructions
38 of 56
IM-PP 599834 0320 ProPress Stainless
Tube Diameter
(inches)
A minimum
(inches)
A minimum
(mm)
B minimum
(inches)
B minimum
(mm)
½ ¾ 19 1⅝ 41
¾ ⅞ 22 2⅛ 54
1 1 26 2½ 64
1¼ 1⅛ 29 2⅞ 73
1½ 1¾ 45 3½ 89
2 2 51 4⅜ 111
Table 16: ProPress standard jaws clearance requirements
Tube
Diameter
(inches)
A
minimum
(inches)
A
minimum
(mm)
B
minimum
(inches)
B
minimum
(mm)
C
minimum
(inches)
C
minimum
(mm)
½ ⅞ 23 1⅜ 35 2½ 64
¾ 1 26 1½ 38 2½ 64
1 1⅛ 29 1¾ 45 3 76
1¼ 1¼ 32 2¼ 57 3⅛ 80
1½ 1⅞ 48 2½ 64 3¾ 95
2 2⅛ 54 3⅛ 80 5 127
Table 17: ProPress standard jaws clearance requirements between tube, wall, and oor
Tube Diameter
(inches)
A minimum
(inches)
A minimum
(mm)
B minimum
(inches)
B minimum
(mm)
½ ¾ 19 2 51
¾
⅞
22 2⅜ 60
1 26 2⅝ 67
1¼ 1⅛ 28 3⅛ 85
Table 18: ProPress compact jaws clearance requirements
Tube
Diameter
(inches)
A
minimum
(inches)
A
minimum
(mm)
B
minimum
(inches)
B
minimum
(mm)
C
minimum
(inches)
C
minimum
(mm)
½ ⅞ 23 1⅜ 35 2½ 64
¾ 1 26 1½ 38 2¾ 70
1 1⅛ 29 1⅝ 41 3 76
1¼ 1⅝ 39 2⅛ 53 3⅜ 85
Table 19: ProPress compact jaws clearance requirements between tube, wall, and
oor
A
B
A
B
C
20°
A
B
A
B
C
20°