Install Instructions

Table Of Contents
Product Information
10 of 56
IM-PP 599834 0320 ProPress Stainless
Media
1
System Operating Conditions
Product Line, Material, and Sealing
Element
2
ProPress Stainless
304 316
Comments
Max Pressure
(psig)
Temperature
Range (°F)
FKM EPDM FKM
Gases
Compressed Air
Oil Concentration ≤25 mg/m
3
200
Max 140°
Oil Concentration >25 mg/m
3
Nitrogen - N
2
Carbon Dioxide - CO
2
Dry
Argon - Ar
Ammonia Anhydrous Max 120°
Oxygen - O
2
Non-medical. Keep free of oil and grease
Max 140°
Hydrogen - H
2
140
Acetylene Test pressure 350 psi 125 Ambient
6
Vacuum
Minimum absolute pressure
750µm Hg Max 160°
Special Media
Methanol
200
75°
Latex Paint 32° to 250°
Urea Solution Concentration ≤40%
140
100°
Caustic Soda Concentration ≤50% 140°
Acetone Liquid 70 -14° to 104°
1
It is recommended that all systems be clearly labeled with the media being conveyed. For further information please consult Viega
Technical Services.
2
All Viega systems must be used with the manufacturer's recommended sealing element.
Contact your local Viega representative or Viega Technical Services for speci󶈵c application temperature, pressure, and concentration limits.
3
System pressure and temperature ranges depend on sealing element. Any ranges listed above will be overruled by the sealing element
limits here:
3a
EPDM temperature ranges are typically 0°F to 250°F.
3b
FKM temperature ranges are typically 14°F to 284°F with temperature spikes (24hr) up to 356°F.
3c
HNBR temperature ranges are typically -40°F to 180°F.
4
System must contain adequate condensate drainage.
5
Ambient temperatures should be taken as normal operating conditions for the applications not to exceed sealing element limitations.
Table 2: ProPress stainless approved gases
DANGER!
Failure to verify suitability
Failure to verify suitability of the system for certain
applications may cause serious personal injury or even death.
It is the responsibility of designers to verify the suitability of type
304 or 316 stainless steel tubing for use with intended 󶈶uid media.
The 󶈶uid's chemical composition, pH level, operation temperature,
chloride level, oxygen level, and 󶈶ow rate and their e󶈴ects on AISI
type 304 stainless steel and/or type 316 stainless steel must be
evaluated by the material speci󶈵er to con󶈵rm adequate system life.
The use of the system for applications other than those
listed or outside of these parameters must be approved by
the Viega Technical Services Department.