IM-PP 599834 0320 ProPress Stainless
2.3 Approved Applications
ProPress 304 FKM and 316 tubing and 󶈵ttings are physically and
chemically compatible with one another. Care must be taken to
ensure that both alloys are compatible with the 󶈶uid and that the
proper sealing elements are used throughout the system.
Media
1
System Operating Conditions
Product Line, Material, and
Sealing Element
2
ProPress Stainless
304 316
Comments
Max Pressure
(psig)
Temperature
Range (°F)
FKM EPDM FKM
Water/Liquids
Hot and cold potable water Test pressure 600 psi
200
See note
3
Rainwater / Graywater
Chilled Water ≤50% Ethylene / Propylene glycol
Hydronic Heating Water ≤50% Ethylene / Propylene glycol
Treated Water
Fully desalinated, deionized,
demineralized, distilled (open system)
Reverse Osmosis Water <1 MΩ
Para󶈷n Wax
Methyl Ethyl Ketone
Isopropyl alcohol
Nitric Acid Concentration ≤10%
Phosphoric Acid Concentration ≤25%
Fire Sprinkler NFPA 13, 13D, 13R 175 Ambient
5
Steam
Low-pressure 15 Max 250°
4
4
Residential 5 Max 227°
4
4
4
Fuels/Oils/Lubricants
Ethanol Pure grain alcohol
200
Ambient
5
Mineral Oil
Lube Oil Petroleum based
Max 150°
Biodiesel 140
Heating Fuel Oil
125
Max 100°
Diesel Fuel
Kerosene Max 68°
1
It is recommended that all systems be clearly labeled with the media being conveyed. For further information please consult Viega
Technical Services.
2
All Viega systems must be used with the manufacturer's recommended sealing element.
Contact your local Viega representative or Viega Technical Services for speci󶈵c application temperature, pressure, and concentration limits.
3
System pressure and temperature ranges depend on sealing element. Any ranges listed above will be overruled by the sealing element
limits here:
3a
EPDM temperature ranges are typically 0°F to 250°F.
3b
FKM temperature ranges are typically 14°F to 284°F with temperature spikes (24hr) up to 356°F.
3c
HNBR temperature ranges are typically -40°F to 180°F.
4
System must contain adequate condensate drainage.
5
Ambient temperatures should be taken as normal operating conditions for the applications not to exceed sealing element limitations.
Table 1: ProPress stainless approved 󶈶uids