Install Instructions
Table Of Contents
- ProPress stainless approved fluids
- ProPress stainless approved gases
- Dimensional data
- ½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- ¾" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1¼" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2½" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 3" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 4" Stainless Steel, ASTM A554 flow rate, velocity, loss
- Fitting friction loss equivalent length of tube (feet)
- MSS SP-58 or the maximum spacing and minimum rod sizes
- Minimum distance between press fittings
- ProPress standard jaws clearance requirements
- ProPress standard jaws clearance requirements between tube, wall, and floor
- ProPress compact jaws clearance requirements
- ProPress compact jaws clearance requirements between tube, wall, and floor
- ProPress rings dimensions
- ProPress rings with V1 actuator clearance requirements
- ProPress rings with V2 actuator clearance requirements
- ProPress rings with V1 actuator clearance requirements between tube, wall, and floor
- ProPress rings with V2 actuator clearance requirements between tube, wall, and floor
- ProPress rings with C1 actuator clearance requirements between tube, wall, and floor
- ProPress XL-C rings dimensions
- ProPress XL-C rings clearance requirements
- ProPress XL-C rings clearance requirements between tube, wall, and floor
- Minimum distance between existing soldered or brazed fitting and ProPress fitting
- Minimum distance between soldered fitting and ProPress fitting
- Minimum insertion depths for ProPress Stainless ½" to 2"
- Insertion depths for ProPress Stainless ½" to 2" no-stop couplings
- Minimum insertion depths ProPress Stainless 2½" to 4"
- Insertion depths for ProPress Stainless 2½" to 4" no-stop couplings
- About this Document
- Disclaimer
- Product Information
- Handling Instructions
- Installation Instructions
- Limited warranty
Installation Instructions
41 of 56
IM-PP 599834 0320 ProPress Stainless
■ The minimum clearance requirement when pressing connections near
an existing brazed connection is two tube diameters.
■ To ensure proper sealing of both the soldered and press connections,
a minimum distance when pressing connections near an existing
soldered tting must be maintained.
Refer to the table below.
4.4 Soldering or Brazing
4.4.1 Using ProPress Stainless In Line with Existing Fittings
Check the tting to make sure there is no residual solder
or other foreign debris on the tube that will be inserted into
the Viega ProPress Stainless tting.
To prevent damage to the sealing element and ensure proper sealing
of the soldered/brazed joint and the press connection, maintain proper
soldering/brazing distances from the tting:
■ When soldering near a ProPress connection: three tube diameters.
■ When brazing near a ProPress connection: nine tube diameters.
Refer to the table on the following page.
4.4.2 Soldering or Brazing In Line with Existing ProPress Stainless Fitting
Tube
Diameter
(inches)
Minimum
distance from
Soldered (inches)
Minimum
distance from
Soldered (mm)
Minimum
distance from
Brazed (inches)
Minimum
distance from
Brazed (mm)
½ ¼ 7 1 26
¾ ¼ 7 1½ 38
1
7
/
16
11 2 51
1¼
7
/
16
11 2½ 64
1½ ⅝ 16 3 76
2 ¾ 19 4 102
2½ ¼ 7 5 127
3 ¼ 7 6 153
4 ¼ 7 8 204
Table 29: Minimum distance between existing soldered or brazed tting and ProPress tting