Install Instructions
Table Of Contents
- ProPress stainless approved fluids
- ProPress stainless approved gases
- Dimensional data
- ½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- ¾" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1¼" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2½" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 3" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 4" Stainless Steel, ASTM A554 flow rate, velocity, loss
- Fitting friction loss equivalent length of tube (feet)
- MSS SP-58 or the maximum spacing and minimum rod sizes
- Minimum distance between press fittings
- ProPress standard jaws clearance requirements
- ProPress standard jaws clearance requirements between tube, wall, and floor
- ProPress compact jaws clearance requirements
- ProPress compact jaws clearance requirements between tube, wall, and floor
- ProPress rings dimensions
- ProPress rings with V1 actuator clearance requirements
- ProPress rings with V2 actuator clearance requirements
- ProPress rings with V1 actuator clearance requirements between tube, wall, and floor
- ProPress rings with V2 actuator clearance requirements between tube, wall, and floor
- ProPress rings with C1 actuator clearance requirements between tube, wall, and floor
- ProPress XL-C rings dimensions
- ProPress XL-C rings clearance requirements
- ProPress XL-C rings clearance requirements between tube, wall, and floor
- Minimum distance between existing soldered or brazed fitting and ProPress fitting
- Minimum distance between soldered fitting and ProPress fitting
- Minimum insertion depths for ProPress Stainless ½" to 2"
- Insertion depths for ProPress Stainless ½" to 2" no-stop couplings
- Minimum insertion depths ProPress Stainless 2½" to 4"
- Insertion depths for ProPress Stainless 2½" to 4" no-stop couplings
- About this Document
- Disclaimer
- Product Information
- Handling Instructions
- Installation Instructions
- Limited warranty
Product Information
22 of 56
IM-PP 599834 0320 ProPress Stainless
Friction loss state within the following tables is based on pipe dimensional
data using the Darcy-Weisbach equation:
h
f
= f • L • V²
D 2
g
2.6.1 Flow Rate, Velocity, and Friction Loss (Water)
Where:
h
f
= friction loss
L = pipe length
D = pipe ID
V = velocity (ft./sec.)
g = gravity constant (32.174ft./sec.²)
f = pipe friction factor
Flow Rate (gpm)
Schedule 5
Wall Thickness = 0.065
ID = 0.50
Velocity (ft./second) Pressure Loss (psi/100 ft.)
1.00 1.63 0.95
2.00 3.27 3.79
3.00 4.90 8.54
4.00 6.54 15.18
5.00 8.17 23.71
6.00 9.80 34.15
7.00 11.44 46.48
8.00 13.07 60.71
9.00 14.71 76.83
10.00 16.34 94.86
11.00 17.97 114.77
12.00 19.61 136.59
13.00 21.24 160.31
14.00 22.88 185.92
15.00 24.51 213.42
16.00 26.14 242.83
17.00 27.78 274.13
18.00 29.41 307.33
Table 4: ½" Stainless Steel, ASTM A312 ow rate, velocity, loss