Install Instructions
Table Of Contents
- ProPress stainless approved fluids
- ProPress stainless approved gases
- Dimensional data
- ½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- ¾" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1¼" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2½" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 3" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 4" Stainless Steel, ASTM A554 flow rate, velocity, loss
- Fitting friction loss equivalent length of tube (feet)
- MSS SP-58 or the maximum spacing and minimum rod sizes
- Minimum distance between press fittings
- ProPress standard jaws clearance requirements
- ProPress standard jaws clearance requirements between tube, wall, and floor
- ProPress compact jaws clearance requirements
- ProPress compact jaws clearance requirements between tube, wall, and floor
- ProPress rings dimensions
- ProPress rings with V1 actuator clearance requirements
- ProPress rings with V2 actuator clearance requirements
- ProPress rings with V1 actuator clearance requirements between tube, wall, and floor
- ProPress rings with V2 actuator clearance requirements between tube, wall, and floor
- ProPress rings with C1 actuator clearance requirements between tube, wall, and floor
- ProPress XL-C rings dimensions
- ProPress XL-C rings clearance requirements
- ProPress XL-C rings clearance requirements between tube, wall, and floor
- Minimum distance between existing soldered or brazed fitting and ProPress fitting
- Minimum distance between soldered fitting and ProPress fitting
- Minimum insertion depths for ProPress Stainless ½" to 2"
- Insertion depths for ProPress Stainless ½" to 2" no-stop couplings
- Minimum insertion depths ProPress Stainless 2½" to 4"
- Insertion depths for ProPress Stainless 2½" to 4" no-stop couplings
- About this Document
- Disclaimer
- Product Information
- Handling Instructions
- Installation Instructions
- Limited warranty
Installation Instructions
37 of 56
IM-PP 599834 0320 ProPress Stainless
4.3.1 Transition Fittings
4.3.1.1 Threaded Connections
The Viega ProPress Stainless systems can be joined with compatible,
o-the-shelf threaded ttings.
In this regard:
■ The threaded connection is made rst.
■ The press connection is made second.
This process avoids unnecessary torsion on the press tting.
4.3.1.2 Flange Connections
When using Viega anges, bolt the ange end in place prior to pressing the
tting to the tube.
4.3.2 Minimum Distance between Fittings
To ensure a correct press, a minimum distance between press ttings must
be maintained. Failure to provide this distance may result in an improper seal.
For installations where the minimum distance is zero, it is particularly
important to ensure the correct insertion depth of the tube into each tting.
Tube Diameter (inches) A minimum (inches) A minimum (mm)
½
0 0¾
1
1¼
7
/
16
10
1½ ⅝ 15
2 ¾ 20
2½
⅝ 153
4
Table 15: Minimum distance between press ttings
minimum
distance
4.3.3 ProPress Jaws Clearance Requirements
The minimum distance between adjacent tubes, or the tube and the wall/ceiling
construction, must be taken into consideration in the planning phase for a
problem free work process. The following illustrate the clearance requirements
for the jaws and ttings and the procedure for pressing ttings in tight quarters.
Tubing installed too closely together
Connection may leak
■ Adhere to minimum intervals between ttings.
■ Insert tube to full insertion depth before pressing.