Install Instructions
Table Of Contents
- ProPress stainless approved fluids
- ProPress stainless approved gases
- Dimensional data
- ½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- ¾" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1¼" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 1½" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2" Stainless Steel, ASTM A312 flow rate, velocity, loss
- 2½" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 3" Stainless Steel, ASTM A554 flow rate, velocity, loss
- 4" Stainless Steel, ASTM A554 flow rate, velocity, loss
- Fitting friction loss equivalent length of tube (feet)
- MSS SP-58 or the maximum spacing and minimum rod sizes
- Minimum distance between press fittings
- ProPress standard jaws clearance requirements
- ProPress standard jaws clearance requirements between tube, wall, and floor
- ProPress compact jaws clearance requirements
- ProPress compact jaws clearance requirements between tube, wall, and floor
- ProPress rings dimensions
- ProPress rings with V1 actuator clearance requirements
- ProPress rings with V2 actuator clearance requirements
- ProPress rings with V1 actuator clearance requirements between tube, wall, and floor
- ProPress rings with V2 actuator clearance requirements between tube, wall, and floor
- ProPress rings with C1 actuator clearance requirements between tube, wall, and floor
- ProPress XL-C rings dimensions
- ProPress XL-C rings clearance requirements
- ProPress XL-C rings clearance requirements between tube, wall, and floor
- Minimum distance between existing soldered or brazed fitting and ProPress fitting
- Minimum distance between soldered fitting and ProPress fitting
- Minimum insertion depths for ProPress Stainless ½" to 2"
- Insertion depths for ProPress Stainless ½" to 2" no-stop couplings
- Minimum insertion depths ProPress Stainless 2½" to 4"
- Insertion depths for ProPress Stainless 2½" to 4" no-stop couplings
- About this Document
- Disclaimer
- Product Information
- Handling Instructions
- Installation Instructions
- Limited warranty
Product Information
21 of 56
IM-PP 599834 0320 ProPress Stainless
■ As long as the tubing is properly prepped and marked
and the tting is installed according to Viega’s
ProPress Stainless Product Instructions, if there is any
deection present after the installation of the tting,
the connection is still acceptable and meets Viega’s
manufacturing specications for proper installation and
warranty.
■ Deection of a press connection has no eect on the
integrity of the system, and it can be pressure tested
in accordance with the ProPress Stainless Product
Instructions.
Re-Press
▶ Press the tting, once on each side (that is, re-press the tting a
second time on the opposite side). Pressing the same connection
from the opposite side will usually straighten misalignment between
the tube and tting.
■ When pressing overhead piping, it may be inconvenient to alternate
sides for each press.
■ The natural weight of the piping plus pressing on opposite sides at a
45 degree angle should adequately eliminate deection.
■ This technique can also be used for any horizontal piping and also
when working above the piping.
2.6 ProPress Stainless Flow Data
Nominal Tube Size
(inches)
Weight
Tube (lb./ft.) Water (lb./ft.) Total (lb./ft.)
½ 0.41 0.06 0.47
¾ 0.59 0.12 0.71
1 0.77 0.20 0.97
1¼ 0.95 0.31 1.26
1½ 1.13 0.43 1.56
2 1.50 0.76 2.26
2½ 2.18 1.61 3.79
3 2.60 2.29 4.89
4 3.46 4.06 7.52
Table 3: Dimensional data