For Types K, L and M Hard Copper Tubing in 1/2” to 2” and Soft Copper Tubing in 1/2” to 1-1/4”.
This Product Contains Zero Lead.
XL-C
Read, understand and follow all instructions for installing ProPress XL-C fittings. Failure to
follow all instructions may result in extensive property damage, serious injury or death.
1. Cut copper tubing at right angles using displacement type cutter or ne-toothed steel saw.
2. Keep end of tubing a minimum of 4” away from the contact area of the vise to prevent possible damage to the tubing in
the press area.
3. Remove burr from inside and outside of tubing to prevent cutting sealing element.
4. Check seal and grip ring for correct t. Do not use oils or lubricants. Use only ProPress Shiny Black EPDM sealing elements.
5. Mark proper insertion depth as indicated by the ProPress XL-C Insertion Depth Chart. Improper insertion depth may result in
an improper seal.
6. Illustration demonstrates proper t of grip ring, separation ring and sealing element.
7.
While turning slightly, slide press tting onto tubing to the marked depth. End of tubing must contact stop.
8. ProPress XL-C tting connections must be performed with ProPress XL-C Rings and V2 ACTUATOR. Use of ProPress XL
Rings and/or Actuator (for Bronze ttings) will result in an improper connection. See Ridgid Operator’s Manual for proper
tool instructions.
9. Open XL-C Ring and place at right angles on the tting. XL-C Ring must be engaged on the tting bead. Check insertion
depth.
10. With V2 ACTUATOR inserted into the tool, open the V2 ACTUATOR as shown and connect V2 ACTUATOR to the XL-C
Ring.
11. Place V2 ACTUATOR onto XL-C Ring and start pressing process. Hold the trigger until the Actuator has engaged the
XL-C Ring. Keep extremities and foreign objects away from XL-C Ring and V2 ACTUATOR during pressing operation to
prevent injury or incomplete press.
12. Release V2 ACTUATOR from XL-C Ring and then remove the XL-C Ring from the tting on completion of press. Remove
tag from tting indicating press has been performed.
1
2
3 5
6
7
8
9
10
11
12
ProPress XL-C Insertion Depth Chart
Tube Size 2-1/2” 3” 4”
Insertion Depth 1-5/8” 1-7/8” 2-3/8”
Pressure Testing: Pressure testing is to be carried out in accordance with local codes. ProPress XL-C includes the Smart
Connect (SC) Feature providing quick and easy identication of unpressed connections during the pressure testing process.
Unpressed connections are located by pressurizing the system with air or water. When testing with air the pressure
range is 1/2 PSI to 85 PSI maximum. When testing with water the pressure range is 15 PSI to 85 PSI maximum. The
SC Feature is an integral part of the design of the tting assuring leakage of liquids and/or gases from inside the system past
the sealing element of an unpressed connection. The SC Feature is removed during the pressing process creating a leak-
proof, permanent connection.
4
“Zero Lead” identies Viega products meeting the lead free requirements of California and Vermont law, effective
January 1, 2010, as tested and listed against NSF- 61, Annex G.