Viega PureFlow System Design Considerations
30 of 88
IM-PF 724596 1021 PureFlow Water System (EN)
The general sizing information shown may be appropriate for many
ManaBloc installations. These recommendations are based on ow rates
of typical xtures that require 8 psi residual pressure.
The length of distribution tubing run between the Viega ManaBloc and
each xture shall be 60 feet or less to maximize optimal performance of
the ManaBloc system. Exceeding this recommended distance aects
the system’s ability to eciently deliver hot water, lengthening the time it
takes for hot water to reach the xture as well as increasing water waste.
6.4 ManaBloc
6.4.1 Supply and Distribution Line Sizing
The best water and energy savings of a ManaBloc system are realized
when distribution lines are sized according to the xture demand and the
length of the individual line. Viega recommends the following tube sizing:
Typical supply line size:
■ ¾" up to 2½ baths
■ 1" up to 4½ baths
Typical distribution line size:
■ ⅜" up to 2½ GPM xture ow requirement (lavs, toilets, bidets, bar
sinks, kitchen sinks, dishwashers)
■ ½" up to 4 GPM xture ow requirement (hose bibbs, tubs, showers,
washing machines, whirlpool baths, soaking tubs, etc.)
Consult the xture manufacturer’s literature to determine the actual
ll rate and residual pressure requirements for distribution line size.
In addition, conrm with local Authority Having Jurisdiction (AHJ) for
acceptable PEX tubing size.
Hose Bibb Note: If a hose bibb is primarily for irrigation purposes, it
should be supplied from the main service line prior to the ManaBloc.
Viega PureFlow Press and PureFlow Crimp ManaBlocs come with ½"
ports that are designed to t both ⅜" and ½" PureFlow port adapters.