Fastening the Viega PureFlow System
70 of 88
IM-PF 724596 1021 PureFlow Water System (EN)
12.10.5 U-Type Expansion Oset
The U-type expansion loop integrates four 90° elbows that form a “U”
pattern.
With this arrangement ⅕ of the “L” dimension is applied as the width
(represented as L3) while ⅖ of “L” is applied as each leg in the other
dimension (represented as L4).
Calculate the necessary L3 and L4 dimensions or use the chart below,
which was gured using the maximum run for a single expansion
compensator (50 feet).
L = 20.7"
L3 = ⅕ (L)
L3 = 20.7"/5 = 4.14"
L3 = 4.14"
L4 = ⅖ (L)
L4 = 2(20.7")/5 = 8.28"
L4 = 8.28"
The fastener shown on the L3 leg may be required to provide additional support depending on how the expansion loop is installed (horizontal/vertical).
U-Type Expansion Oset (inch) per 50 linear feet of run
Tubing
ΔT(° F)
Tube
nom.
60 80 100 120 140 160 180 200
L3 L4 L3 L4 L3 L4 L3 L4 L3 L4 L3 L4 L3 L4 L3 L4
Viega
PureFlow
PEX
¾" 4.1 8.2 4.7 9.4 5.3 10.5 5.8 11.6 6.2 12.5 6.7 13.3 7.0 14.2 7.5 14.9
1" 4.6 9.3 5.3 10.7 6.0 12.0 6.6 13.1 7.1 14.2 7.6 15.1 8.0 16.0 8.5 16.9
1¼" 5.1 10.2 5.9 11.8 6.6 13.2 7.2 14.5 7.8 15.6 8.4 16.7 8.9 17.7 9.4 18.7
1½" 5.6 11.1 6.4 12.9 7.2 14.4 7.9 15.7 8.5 17.0 9.1 18.2 9.6 19.3 10.2 20.3
2" 6.4 12.7 7.4 14.7 8.2 16.4 9.0 18.0 9.7 19.5 10.4 20.8 11.0 22.1 11.6 23.2
U-Type Looped Oset
L3
L4L4
4 - 6" 4 - 6"
∆L/2 ∆L/2
LT
Anchor point Anchor point
U-Type Expansion
L4 = 8.28"
L3 = 4.14"
L4 = 8.28"