Installing the ManaBloc
41 of 88
IM-PF 724596 1021 PureFlow Water System (EN)
ManaBloc Supply Piping Options
Flow-thru piping
(standard)
Non-ow-thru piping
Top supply
(Bull head tee)
Non-ow-thru piping
Top supply
(Standard)
Hot water from W/H
Hot water from W/H
Hot water from W/H
Cold water to W/H
Cold water to W/H
Cold water supply to W/HCold water supply
Bull head tee
End cap End cap
Water service (cold)
Water service (cold)
Water service (cold)
If a main inlet/outlet will not be used, it must be capped. (Use part
number 53601.)
The main service line to the ManaBloc may include a main shuto valve,
as required by local code. Although a shuto valve for the main service
line at the ManaBloc itself is not required, it can be a benecial option for
a homeowner and is recommended.
Local code may also require the installation of a check valve, Pressure
Reducing Valve (PRV), back ow preventer, etc. To prevent debris and
other particles from entering the system, a strainer may be installed in the
service line.
Optional
ManaBloc
shutoff