Minimum distance between two Viega MegaPress
press connections ½" to 2"
Pipe
Diameter
Minimum Distance
(in)
Minimum
Distance
(mm)
½"
3
⁄
16
5
¾"
3
⁄
16
5
1"
3
⁄
16
5
1¼" ⅜ 10
1½" ⅜ 10
2" ⅜ 10
Pipe Size
Insertion Depth (in)
½"
1
1
⁄
16
¾" 1
3
⁄
16
1" 1⅜
1¼" 1⅞
1½" 1⅞
2" 2