Viega MegaPressG Systems
Product Instructions
1. Cut piping at right angles using displacement type
cutter.
2. Keep end of piping a minimum of 4" away from the
contact area of the vise to prevent possible damage
to the piping in the press area. See RIDGID Manual for
minimum clearance required for prep tools.
3. Remove burr from inside and outside of piping and
prep to proper insertion depth using a preperation tool
or fine grit sandpaper.
4. Check seal and grip ring for correct fit. Do not use oils
or lubricants.
5. Illustration demonstrates proper fit of grip ring,
separation ring and sealing element.
6. Mark proper insertion depth. Improper insertion depth
may result in an improper seal. The depth marking
shall be visible on the completed assembly.
7a. Viega
®
MegaPress
®
½" - 1" fitting connections must
be performed with MegaPress Jaws. See Ridgid
Operator’s Manual for proper tool instructions.
7b. Open the MegaPress Jaw and place at right angles on
the fitting. Visually check insertion depth using mark
on piping.
7c. Start pressing process and hold the trigger until the jaw
has engaged the fitting. Keep extremities and foreign
objects away from MegaPress Jaw during pressing
operation to prevent injury or incomplete press.
8a. Viega MegaPress 1¼" - 2" fitting connections must
be performed with MegaPress Rings and V2 Actuator.
See Operator’s Manual for proper tool instructions.
8b. Open MegaPress Ring and place at right angles on the
fitting. MegaPress Ring must be engaged on the fitting
bead. Check insertion depth.
8c. Place V2 Actuator onto MegaPress Ring and start
pressing process. Hold the trigger until the Actuator
has engaged the MegaPress Ring. Keep extremities
and foreign objects away from MegaPress Ring and
V2 Actuator during pressing operation to prevent injury
or incomplete press.
9. Remove MegaPress Jaw from fitting or release V2
Actuator from RIDGID MegaPress Ring and then
remove MegaPress Ring from the fitting on completion
of press. Remove control label to indicate press has
been completed
Note: The installation, inspection, testing and purging
of the fuel gas system shall be in accordance with local
codes, or, in the absence of local codes, in accordance
with the International Fuel Gas Code, NFPA 54/National
Fuel Gas Code z223.1, the Uniform Plumbing Code, NFPA
58, or CSA B 149.1 as applicable.
CAUTION:
(a) The fittings are for use with fuel gases and are
intended for the operating pressure 0-125 psi.
(b) The fuel gas system shall not be used as a grounding
electrode for an electrical system.
1
4
9
8A
7A
2
5
8B
7B
3
6
8C
7C