Install Instructions

95
IM-PR 566442 1114 (Design Manual)
4.2.4 Considerations for slabs
Warming Up the Slab
When starting up an in-slab system in heating
mode for the first time, it is best to warm the
thermal mass up slowly to help prevent possible
shock to the slab. In accordance with DIN 4725
section 4, Viega recommends:
Start warmup after concrete has reached its
final set (curing complete).
Set supply water temperature to 77°F for the
first three days.
Increase supply water temperature to the set
point in gradual increments for the next four
days (maximum of a 50°F increase in a period
of 24 hours).
Slab warmup should follow the concrete
manufacturer’s recommendations.
Testing for excessive moisture
Prior to installing a floor covering on a radiant-
heated slab, ensure that the slab has cured
sufficiently. One easy way to confirm this is through
a polyethylene film test:
Tape a one-foot square of 6 mil clear polyethylene
film to slab, sealing all edges with plastic moisture-
resistant tape. If, after 48 hours, there is no
“clouding” or drops of moisture on the underside
of the film, the slab can be considered dry
enough for finish floor applications. Drying times
vary considerably with location, season, interior
temperature/humidity, etc. Follow the finish flooring
manufacturer’s recommendations.
31. ©CSA Group, B214-12. 2012. “Installation Code for Hydronic Heating Systems” Clause 4.6.2
(CSA B214, Clause 4.6.2)
The installer shall ensure that the system
documentation and manufacturer’s operational
instructions are left near the primary heating
equipment or, if that is not practical, near the main
electrical distribution panel, in order for service
and maintenance personnel to have access to the
documentation and instructions.
NOTES:
(1) Examples of information that should be
provided in the documentation of the system
for hydronic space heating include
(a) a room-by-room heat loss calculation in kW
(Btu/h);
(b) the heat output of the heat-distribution unit
in kW (Btu/h);
(c) the system design water temperatures in
°C (°F);
(d) the pipe size in mm (nominal size NPS, in)
and total length of piping in m (ft); and
(e) the system head loss and flow rates in kPa
and L/s (psi and gpm).
(2) Examples of information that should be
provided in the documentation of the system
for radiant heating include
(a) a room-by-room heat loss calculation in
kW (Btu/h);
(b) the floor area in m
2
(ft
2
);
(c) the total usable panel area in m
2
(ft
2
);
(d) the heat output density in W/m’ ((Btu/h)/fi
2
)
of panel area;
(e) the radiant heating panel supply water
temperature in °C (°F);
(f) the pipe size in mm (nominal size NPS, in),
maximum spacing between the lengths of
piping in mm (in), and total length of piping
in m (ft);
(g) the minimum number of heating loops;
(h) the boiler supply water temperature in °C
(°F);
(i) the auxiliary heat required in kW (Btu/h);
(j) the RSI value in m"K/W (R-value) of the
floor coverings;
(k) the RSI value m’.K/W (R-value) of the
insulation under and at the edges of the
radiant panel;
(I) the outdoor design temperature in °C (°F);
(m) the floor surface temperatures in °C (°F):
and
(n) the system friction loss and flow rate in
kPa and L/s (psi and gpm).
(3) Additional information for documentation of the
system is presented in Figures A.1 and A.2.
(4) Attempts should be made to instruct the
user in the safe and correct operation of the
system.
31
4.2.5 System documentation and operational instructions