Install Instructions
IM-PR 566442 1114 (Design Manual)
84
plant may be able to run at a higher efficiency by
delivering its chilled water to the radiant panel at
a higher supply temperature (i.e., 55 to 60°F) than
would be required for a water to air heat exchanger
(~45°F). Higher supply temperatures increase a
radiant cooling system’s efficiency by increasing
the effective operating range for water-side
economizing and by permitting a higher evaporative
temperature for the chiller.
22
Latent cooling
Controlling indoor humidity reduces the chance
of undesired condensation on building surfaces,
such as floors. Equipment options to satisfy latent
loads and simultaneously control the dewpoint of a
space include:
• Mechanical systems with refrigerant (direct
expansion) or chilled water
• Desiccants - liquid or solid sorption
Mechanical dehumidifiers blow moisture-laden air
over coils that contain chilled refrigerant or water
at a temperature below the air’s dewpoint. The
moisture in the air condenses on the coil, resulting
in an airstream that has lower moisture content and
is at a lower drybulb temperature. If the drybulb
temperature of this lower-humidity air is below
design conditions, it may be reheated with waste
heat from a refrigeration vapor compression cycle.
Figure 3-7 Rotating horizontal desiccant.
Evaporating refrigerant can cool liquid rather than
air. The liquid is then used to cool air. The design
can cool air close to 32°F without freezing the
condensate, and has the advantage of equalizing
the load on the compressor and condenser when
many different air streams must be cooled by a
single refrigeration system.
24
22. Doebber, I., M. Moore, M. Deru. 2010. “Radiant Slab Cooling for Retail.” ASHRAE Journal 52(12):28-37.
23. Harriman III, Lewis G. 1989. The Dehumidification Handbook (Second Edition) p. 24
24. Harriman III, Lewis G. 1989. The Dehumidification Handbook (Second Edition) p. 26
25. ASHRAE Handbook – HVAC Systems and Equipment. 2008.
Desiccants provide dehumidification through liquid
or solid sorption. Liquid sorption conditioners use
a working solution that is typically composed of
lithium chloride or glycol, which has a very high
affinity for water vapor. In solid sorption, humid air
passes through an “active” desiccant. The lower
vapor pressure of the active desiccant results in
transfer of vapor from the air to the desiccant. The
saturated desiccant is then heated to release the
moisture into a separate air stream (the reactivation
air) that has a lower vapor pressure than the
desiccant.
25
A typical solid-sorption application is a
rotating horizontal bed (Figure 3-8).
Compressor raises
the pressure and
temperature of the
refrigerant gas
Refrigerant con-
densed back to a
liquid, releasing its
heat to the air passing
through the condens-
er coil.
Refrigerant expands inside the coil,
removing heat from the air passing
though the system.
Refrigerant Expansion Valve
Refrigerant CondenserCompressor
Liquid Refrigerant Storage
Refrigerant Expansion Valve
Compressor Refrigerant Condenser
Liquid Refrigerant Storage
Chilled water
Refrigerant - water heat exchanger
Water chilled by the refrigeration system
is circulated through the cooling coil that
chills and dehumidies the air.
Figure 3-6 Dehumidification with refrigerant.
Refrigeration systems transfer heat from one
airstream to another very efficiently, cooling one
and heating the other. This is the basis for most
cooling-based dehumidification systems.
23