Install Instructions
IM-PR 566442 1114 (Design Manual)
80
Figure 3-4 Percent persons dissatisfied (PPD) based on floor temperature. Note that a minimum of ~66°F is
advisable to achieve 10 PPD
20
41
50 59 68 77 86 95 104 °F
510152025303540
°C
1
2
4
6
8
10
20
40
60
80
%
FLOOR TEMPERATURE
LOCAL DISCOMFORT CAUSED BY
WARM AND COOL FLOORS
DISSATISFIED
Dewpoint temperature: When a surface temperature
is below the dewpoint temperature of the
surrounding air, condensation is likely to occur
on the surface. Generally speaking, as the relative
humidity of a space decreases, the dewpoint
temperature also decreases. A lower dewpoint
means a lower likelihood of condensation. If you
know the relative humidity and drybulb temperature
of a space, you can determine its dewpoint
temperature through referencing a psychrometric
calculator or a psychrometric chart.
Dewpoint temperature can be proactively controlled
through providing dehumidification to a space, as
explained in Section 3.6.3. To avoid condensation,
the dewpoint should be controlled to remain lower
than the supply temperature to a space.
Temperature drop: To support delivery of high
supply temperatures, which can provide higher
system efficiency, a temperature drop of 5 to 10°F
is recommended for commercial cooling.
Supply temperature: In radiant cooling, it is
advisable to maintain supply temperatures as
high as possible while still meeting design load
requirements for the space. Supplying higher
temperatures to the zone permits increases
in the efficiency of the cooling equipment and
reduces the risk of condensation when the supply
temperature is below the space dewpoint. The
trade-offs for supplying higher temperatures are
higher flow rates, higher head and potentially
tighter spacing requirements for the tubing (e.g.,
6" to 9"). Table 3-7 shows required mean cooling
water temperatures as a function of floor covering
R-value, thickness of concrete above the tubing,
tubing spacing and targeted cooling capacity.
Mean cooling water temperatures represent the
average water temperature in a panel. Supply
temperature can be calculated from the mean
cooling water temperature using the following
equation:
Ts =
∆T
2
MCWT
—
where:
Ts = Supply temperature (°F)
MCWT = Mean cooling water temperature (°F)
∆T = Temperature drop across the panel
20. ©ASHRAE BSR/ASHRAE Standard 55P, Thermal Environmental Conditions for Human Occupancy