Install Instructions

IM-PR 566442 1114 (Design Manual)
44
U-type expansion loop:
The U-type expansion loop integrates four 90° elbows that form a “U” pattern.
With this arrangement of the “L” dimension is applied as the width (represented as L3) while of “L” is
applied as each leg in the other dimension (represented as L4).
Calculate the necessary L3 and L4 dimensions or use the chart below, which was gured using the maxi-
mum run for a single expansion compensator (50 ft.).
L = 19.30"
L3 = (L)
L3 = 19.30"/5 = 3.86"
L3 = 3.86"
L4 = (L)
L4 = 2(19.30")/5 = 7.72"
L4 = 7.72"
U-Type Expansion Loop (in)
per 50 linear feet of run
Tubing
∆T(°F)
Tube
nom.
60 80 100 120 140 160 180 200
L3 L4 L3 L4 L3 L4 L3 L4 L3 L4 L3 L4 L3 L4 L3 L4
ViegaPEX
&
ViegaPEX
Ultra
¾" 4.1 8.2 4.7 9.4 5.3 10.5 5.8 11.6 6.2 12.5 6.7 13.3 7.0 14.2 7.5 14.9
1" 4.6 9.3 5.3 10.7 6.0 12.0 6.6 13.1 7.1 14.2 7.6 15.1 8.0 16.0 8.5 16.9
1¼" 5.1 10.2 5.9 11.8 6.6 13.2 7.2 14.5 7.8 15.6 8.4 16.7 8.9 17.7 9.4 18.7
1½" 5.6 11.1 6.4 12.9 7.2 14.4 7.9 15.7 8.5 17.0 9.1 18.2 9.6 19.3 10.2 20.3
2" 6.4 12.7 7.4 14.7 8.2 16.4 9.0 18.0 9.7 19.5 10.4 20.8 11.0 22.1 11.6 23.2
ViegaPEX
Barrier
¾" 3.8 7.6 4.4 8.8 4.9 9.8 5.4 10.8 5.8 11.6 6.2 12.4 6.6 13.2 7.0 13.9
1" 4.3 8.6 5.0 10.0 5.6 11.2 6.1 12.2 6.6 13.2 7.1 14.1 7.5 15.0 7.9 15.8
1¼" 4.8 9.6 5.5 11.0 6.2 12.3 6.8 13.5 7.3 14.6 7.8 15.6 8.3 16.5 8.7 17.4
1½" 5.2 10.4 6.0 12.0 6.7 13.4 7.3 14.7 7.9 15.9 8.5 17.0 9.0 18.0 9.5 19.0
2" 5.9 11.9 6.9 13.7 7.7 15.3 8.4 16.8 9.1 18.1 9.7 19.4 10.3 20.6 10.8 21.7
Table 1-12 NOTE: This chart was figured using the maximum run for a single expansion compensator (50 ft.). Refer to
Viega installation manuals for recommended operating temperatures, pressures, tubing fasteners and fastener spacing.
L4
L3
L4
4-6" 4-6"
The fastener shown on the L3 leg may be required to provide additional support depending on how the expansion loop is installed
(horizontal / vertical).
Illustration of Example
L4 = 7.72"
L3 = 3.86"
L4 = 7.72"