Install Instructions
IM-PR 566442 1114 (Design Manual)
26
Application Location
On-Center Spacing
(in., typical)
Nominal Tubing Size
(in., typical)
In-Slab
On or Above-Grade Living
Areas
9" ½" or ⅝"*
Below Grade 9" – 12" ½" or ⅝"*
Bathrooms and High-Output
Areas
6" – 9" ⅜" or ½"
Gypsum-concrete
(thin-slab)
6" – 9" ½"
Garages and Workshops, Inte-
rior Zones of Large Commercial
Buildings or Warehouses
12" ½", ⅝", or ¾"
Dry Mass
Above-Suboor Panels 7" – 10"
5
∕
16
"
Below-Suboor (Residential
Only)
8" ⅜" or ½"
Wall Panels 7" – 10"
5
∕
16
"
Table 1-6 Typical spacing and nominal tubing size, by application
*Used more commonly in commercial applications.
Nominal Tube Size, in Maximum Loop Length, m (ft)
¼ 39 (125)
5
/
16
61 (200)
⅜ 76 (250)
½ 91 (300)
⅝ 122 (400)
¾ 152 (500)
1 229 (750)
Tubing ≤ 25 Btu/hr/ft
2
>25 Btu/hr/ft
2
5
∕
16
" 250 200
⅜" 300 250
½" 400 350
⅝" 500 450
¾" 800 750
Table 1-7 Maximum recommended circuit lengths in feet, assuming a temperature drop of ≥ 20°F, 100%
water, and air temperature of 68°F
Table 1-8 Maximum length of continuous tubing from a supply-and-return manifold arrangement
NOTE: Data for this table were compiled by the B214 Technical Committee and are based on
manufacturers’ recommendations and good engineering practice.
7
7. ©CSA Group, B214-12. 2012. “Installation Code for Hydronic Heating Systems” Table 1
Maximum loop lengths
(CSA B214 Table 1) See clause 14.3.2
CSA B214 Clause 14.3.2
The maximum length of continuous tubing from a supply-and-return manifold arrangement
shall not exceed the lengths specied by the manufacturer or, in the absence of manufacturer’s
specications, the lengths specied in Table 1. Actual loop lengths shall be determined by spacing,
number of loops and pressure drop requirements, as specied in the system design.