Install Instructions

177
IM-PR 566442 1114 (Design Manual)
Figure C-1h
Section through joist with heat transfer plate
Be sure to check with local building codes to ensure
no structural damage will occur due to drilling the
joists. Use 1¼" holes at min. 3" from the subfloor to
avoid floor nails. Centered holes would be ideal for
structural strength.
Exterior Wall Member
R-19 Insulation:
Use a Foil Face or Radiant Barrier
to keep a 1" to 2" air gap between
the insulation and the Traks.
Refer to local code for insulation
requirements.
Heat Transfer Plate: 5"W x 19"L
have a 1" gap between Climate
Traks, install 1½" off the joist
Floor Joist
Insulation Blocking
NOTE: Stop plate
installation 12" to 16"
before bend. Minimum 6"
distance off wall. Ensure
turns are not secured.
Tubing Spacing (per design)
Return
Supply
Figure C-1i
Joist space layout — heat transfer plate
Be sure to check with local building codes to
ensure no structural damage will occur due
to drilling the joists. Use 1¼" holes at min. 3"
from the subfloor to avoid floor nails. Centered
holes would be ideal for structural strength.
6" Off Wall
Insulation Blocking
Exterior Wall
NOTE: Stop Trak
installation 12" to 16"
before bend. Ensure
turns are not secured.
8" Spacing (per design)
Interior Wall
Heat Transfer Plate:
5"W x 19"L have a 1" gap between
Climate Traks, install 1½" off joist
SupplyReturn