Install Instructions
IM-PR 566442 1114 (Design Manual)
174
Figure C-1b
Joist space layout -- Climate Trak
Be sure to check with local building codes to
ensure no structural damage will occur due
to drilling the joists. Use 1¼" holes at min. 3"
from the subfloor to avoid floor nails. Centered
holes would be ideal for structural strength.
6" Off Wall
Insulation Blocking
Exterior Wall
NOTE: Stop Trak
installation 12" to 16"
before bend. Ensure
turns are not secured.
8" Spacing (per design)
Interior Wall
Climate Trak:
3½" x 48" or 96" L have a 1" gap
between Climate Traks, install 1½"
off joist
SupplyReturn
Figure C-1c
Joist space section — Climate Trak
Floor Joist
Foil Face or Radiant Barrier:
Keep a 1" to 2" air gap
¾" Plywood
Subfloor
Tubing Spacing (per design)
Climate Trak
R-19: Refer to local code for
insulation requirements.