Install Instructions
13
IM-PR 566442 1114 (Design Manual)
(CSA B214 Clauses 14.4.4.1, 14.4.4.2, 14.5.3 and
14.5.5)
When a poured concrete radiant oor system
is installed in contact with the soil, insulation
that complies with Clause 14.4.4.3 and has a
minimum RSI value of 0.9 m
2
•K/W (R-value of 5
h•ft
2
•°F/ Btu) shall
(a) be placed between the soil and the
concrete;
(b) extend as close as practical to the outside
edges of the concrete; and
(c) be placed on all slab edges.
When a poured concrete radiant oor system is
installed on grade, insulation that complies with
Clause 14.4.4.3 and has a minimum RSI value of
0.9 m
2
•K/W (R-value of 5 h•ft
2
•°F/ Btu) shall be
placed on all vertical slab edges.
When tubing is installed in the joist cavity, the
cavity shall be insulated with material having an
RSI value of at least 2.1 m
2
•K/W (R-value of at
least 12.0 h•ft
2
•°F/Btu).
When tubing is installed above or in the suboor
and not embedded in concrete, the oor
assembly shall be insulated with a minimum total
insulated RSI value of 2.1 m
2
•K/W (R-value of 12
h•ft
2
•°F/Btu) below the tubing.
3
3. ©CSA Group, B214-12. 2012. “Installation Code for Hydronic Heating Systems” Clauses 14.4.4 - 14.5.5
1.3.3 Insulation requirements for Canada