4. Mark proper insertion depth as
indicated by the Sanpress INOX
insertion depth chart. Improper
insertion depth may result in an
improper seal.
5. Check seal and grip ring for correct
fit. Illustration demonstrates proper
fit of grip ring, separation ring and
sealing element. Use only ProPress
shiny black EPDM sealing elements.
6. While turning slightly, slide press
fitting onto piping to the marked
depth. Do not use oils or lubricants.
7. Sanpres INOX fitting connections
must be performed with ProPress XL
Rings and V2 ACTUATOR. Use of
ProPress XL Rings and/or Actuator
(for Bronze fittings) will result in an
improper connection. See
RIDGID
®
Operator’s Manual for proper
tool instructions.
8. Open XL Ring and place at right
angles on the fitting. XL Ring must be
engaged on the fitting bead. Check
insertion depth.
9. With V2 ACTUATOR inserted into
the tool, open the V2 ACTUATOR as
shown and connect V2 ACTUATOR
to the XL Ring.
10. Place V2 ACTUATOR onto XL
Ring and start pressing process.
Hold the trigger until the Actuator
has engaged the XL Ring. Keep
extremities and foreign objects away
from XL Ring and V2 ACTUATOR
during pressing operation to prevent
injury or incomplete press.
11. Release V2 ACTUATOR from XL
Ring and then remove the XL Ring
from the fitting on completion of
press. Remove elastic control ring
from fitting, indicating press has
been performed.
Sanpress XL Insertion Depth Chart
Tube
Size
(mm)
76
88 108
Insertion
Depth
(mm)
50
50 65