User Manual
EN - English - Instructions manual
18
6.2.24 Dip switch SW6 and SW4
configuration table
SW6
Dip Position Function
1 ON PELCO D protocol
1 OFF VIDEOTEC or MACRO
protocols (setting the dip 8
of SW4)
2, 3, 4 Indifferent No function
SW4
Dip Position Function
1, 2 OFF, OFF 9600 baud* (VIDEOTEC and
MACRO), 2400 PELCO D
1, 2 ON, OFF 300 baud VIDEOTEC, 38400
baud MACRO, 4800 baud
PELCO D
1, 2 OFF, ON 1200 baud (VIDEOTEC and
MACRO), 9600 baud PELCO D
1, 2 ON, ON 19200 baud (VIDEOTEC,
MACRO and PELCO D)
3 OFF Unused alarms*
3 ON Used alarms
4 OFF N.C. alarms*
4 ON N.O. alarms
5 OFF -
5 ON Alarms on Aux4
6 OFF -
6 ON To release Aux3 and Aux4
7 OFF -
8 ON** VIDEOTEC standard
protocol****
8 OFF*** MACRO protocol **** ((DCIR,
DCJ, DCT and DCTEL)
Tab. 04 * Default settings.
** Compatible with keyboards DCIR, DCJ, DCT and
DCTEL with VIDEOTEC standard protocol.
*** Compatible with keyboards DCIR, DCJ, DCT and
DCTEL with MACRO protocol.
**** Selectable only if the dip 1 of SW6 is in OFF
position.
6.2.22.1 Example of Patrol sequence
programming.
If you want to set up a Patrol sequence that starts
from Preset position 19, ends at Preset position 33
and stops for one minute at every position reached:
: Enables parameter insertion;
: Start Patrol at position 19;
: End Patrol at position 33;
: Pause of 60 seconds at every position
reached;
: Start of sequence;
: End of sequence.
6.2.23 Switching on and switching off
Before connecting the unit:
• Make sure that the goods supplied correspond
to the required specifications by controlling the
rating plates ("4.2 Product markings", page 7);
• Make sure that the fuses of the EXDTRX3 /
EXDTRX324 receiver are not damaged;
• Make sure that the receiver and the other
components of the plant are closed in order to
avoid the direct contact with live elements;
• Make sure that all parts are accurately and firmly
fixed;
• The power cords must not hamper the normal
operations of the installer and the movement of
the positioning device;
• Make sure that all power sources and the
connecting cables are able to bear the system
consumption.