XOa Client Software User Manual
21796_05_preliminary 99
Note
To activate an output on input I201, open System > Behaviour > Input/Output behaviour,
select an output (filter on Outputs: on the box to see only the physical outputs) and choose
Programmable. Select Active sensor (I201) in the list.
All sensors assigned to an alarm profile that triggers I201, have to return to idle state in order to reset the
selected output. When this condition is fulfilled, the user can arm the video system without triggering a false
alarm.
12.3 Deleting an Alarm Profile
Note
You cannot delete the default alarm profiles, or alarm profiles that are in use (= assigned to
events).
To delete an alarm profile, proceed as follows:
1. Click the alarm profile in the list, and then click Remove.
2. Click Yes to confirm.
3. Click Save.
12.4 Default Profiles
The server comes with 10 standard alarm profiles:
1 – NORMAL EVENT
2 – PRIMARY EVENT
3 – BACKUP EVENT
4 – SILENT MESSAGE
5 – SINGLE EVENT
6 – ACTIVE SENSOR EVENT
7 – FIRE PRIMARY
8 – FIRE ADVISORY
9 – FIRE VERIFICATION
10 – FIRE TROUBLE
Alarm profiles 7–10 are only available if you have installed a SmokeTrace license on your server.