During PIR commissioning, while the walk test port is in use (for example by the iPIR app), the transparent
mode (Transp. Mode) is active. In transparent mode, the RMG does not transmit alarms/events from the
PIR devices to the CMS. This allows for testing and adjusting the PIR devices before going ‘live’.
Click Initiate PIR discovery to search the server for any connected PIR devices. The PIR detector
information panel displays the found PIR devices:
Click Refresh info to search for connected PIR devices again.
Click Clear counters to reset the numbers in the Time outs and Pkt Errors columns.
16.4 Double-Knock Configuration
To reduce the number of false alarms from a PIR, you can use double-knock configuration. In a double-
knock configuration, the double-knock event is only triggered when another trigger occurs simultaneously.
Typically, you combine the PIR with a camera for analytics.
Note
You need to set up the correct alarm profile for the double-knock input so that it transmits the
alarm, and you need to set up the individual inputs so that they do not transmit alarms. For an
overview of the PIR alarm inputs, see PIR Alarms on page 112.
To set up a PIR in a double-knock configuration, proceed as follows:
1. Choose System > Behaviour > PIR Settings, and click Initiate PIR Discovery. The available PIR
devices appear in the Double knock configuration list.